Research Journal of Engineering Sciences _________________________ ______ ____ ________ ISSN 2278 – 9472 Vol. 2 ( 7 ), 10 - 14 , Ju ly (201 3 ) Res. J. Engineering Sci. International Science Congress Association 10 Thermodynamic Modelling of a Vapor Absorption Cogeneration Cycle Agarwal Priyank CO 2 Research and Green Technologies Centre, VIT University, Vellore - 14, INDIA Available online at: www.isca.in Received 10 th June 201 3 , revised 18 th June 201 3 , accepted 22 nd June 201 3 Abstract Attempting towards sustainable development through the principles of cogeneration, proposal towards vapor absorption cogeneration cycle is presented with improved performance efficiency. MATLAB based simulations were done for utilization of condenser as heat rejecter and addition of reheater and other components to conventional absorption refrigeration cycle. The propose d combined heating and cooling cycle demonstrated optimum performan ce at ambient temperature of 20 °C , heat input temperature of 170 °C with 0.96 as weak solution concentration. The energy analysis presented total output of 1286.49kW, including process heat of 732.05 kW with cooling effect of 554.44 kW, with energy utilization factor of 1.193 at best conditions. The proposed cycle calls for further research and development aiming in favor of improvement in efficiency and better performance. Keywords: Modelling, simulation, cogeneration, vapor absorption, heating, cooling . Introduction The level of awareness and cognizance for energy conservation and management among the people has increased rapidly in recent years. Urge for sustainable development, energy safeguarding and diminution of global warming has also encouraged the global level. With modernization and increased standard of living, people demand for comfortable life, but at economical price. This calls for u pgradation of conventional systems and proposal of new technologies as well. Agarwal et al. suggests application of cogeneration principle, but the vapor compression refrigeration cycle requires significant amount of electricity and power 1 . Also, the use o f R134a as working fluid poses threat to environment with very high global warming potential 2 . Focusing upon balanced progression of society and environment, cogeneration presents itself as a potential solution. Increased overall efficiency with minimal c ost involvement has always been considered as prime objective of any technological development. Shankar and Srinivas presents an approach towards combined power and cooling based cogeneration using vapor absorption refrigeration systems 3 . Implementation of absorption system based heat pumps in kraft pulping process by Bakhtiari et al. presents strong advantages of absorption systems for sustainable development 4 . There has been varied use of fluids for vapor absorption refrigeration systems, including NH 3 - H 2 O, LiBr - H 2 O, NH 3 - NaSCN, NH 3 - LiNO 3 etc. Comparing performance of absorption refrigeration systems utilizing ammonia - lithium nitrate, ammonia - water and ammonia - sodium thiocyanate as working fluids, although the variations in results are not notable, ammonia - water cycle has the least coefficient of performance. But, easy and cost - effective commercial availability of NH 3 - H 2 O overshadows the small decrement in performance results. Also, the limitation regarding use of H 2 O as a solvent in working fluid for opera tion at temperatures below 0 °C promotes use of aqua - ammonia over it. As by Billiard, ammonia has strengthened its application as refrigerant in refrigeration systems 5 . In recent times, concept of heat recovery and energy utilization from conventional ene rgy sources has greatly developed. This presents improved overall efficiency for both primary and secondary energy cycles. Srinivas et al. analysed model of a combined cycle with Kalina bottoming cycle and inferred increase in combined cycle efficiency com pared to conventional cycle 6 . Analysis of absorption refrigeration system by Kalinoswki et al. powered with waste heat confirms the cost savings and potential development of the heat recovery cycles 7 . Thus, analysis of an altered aqua - ammonia based absorpt ion refrigeration system utilizing heat recovery was done by the author with implementation of combined cooling and heating cogeneration system. Material and Methods In the present work, incorporation of reheater is done to reheat the weak solution, utilizing heat recovery as primary source. An attempt has also been made to provide process heat by use of condenser as heater. The weak solution rejects heat to air and gets condensed to liquid state. Liquid weak solution, expanded in expansion valve, pro vides cooling effect at evaporator. Use of thermic fluid cycle has been employed to integrate both heat source and cogeneration cycle. Thermodynamic properties of aqua - ammonia mixture were obtained from the work by Xu and Goswami 8 . Research Journal of Engineering Sciences ___________ _________ _____ __________________ ______ ____ ___ ISSN 2278 – 9472 Vol. 2 ( 7 ), 10 - 14 , Ju ly (201 3 ) Res. J. Engineering Sci. International Science Congress Association 11 The schematic flow diagr am of the cogeneration cycle is presented in figure - 1. Compared to conventional vapor absorption refrigeration cycles, an additional heat exchanger has been employed to extract heat from return fluid. With addition of reflex condenser, efficiency of the cy cle increases as it allows almost pure ammonia vapor to flow. With reduced percentage of water, possibilities of blockage in the eva porator at temperatures below 0 °C are reduced. Assumptions considered for the analysis are enlisted below: i. The isentropic efficiency of pump and effectiveness of the heat exchanger are considered as 75 %. ii. The concentration difference between reflux condenser outlet and inlet is considered as 0.08. iii. Degr ee of reheat for reheater is 10 °C. iv. Refrigerant tempera ture en tering evaporator is - 10 °C. v. Absorber exit temperature is 5 °C greater than atmospheric temperature. Vi. 20 °C rise in air temperature from atmospheric condition is considered for heater, while air temperature at exit of evaporator is - 10 °C. Figure - 1 S chematic flow diagram of proposed cogeneration cycle For performance analysis of the vapor absorption cogeneration system, equations (1) to (9) were used to determine the mass flow rate, concentration or enthalpy of mixture at specified point. Heat content of the mixture at pressurized state, after pump, is given by equation (1). Equation (2) gives the mass flow rate of reject fluid after separator, while (3) presents the mass of mixture entering reflex condenser. Weak solution implies mixture with very hig h concentration of ammonia. For varying concentration of weak solution from 0.96 to 0.99, mass flow after the reflex condenser is given by equation (4). Equation (5) gives the reject mass from reflex condenser, which mixes with separator reject. Equation ( 6) yields total mass of reject fluid and (7) gives the concentration. Equation (8) gives net heat content of the reject mixture. Enthalpy of mixture after pump, (1) Mass of reject fluid from separator, (2) Mass of mixture entering reflex condenser, (3) Mass of weak solution after reflex condenser, (4) Reject mass from reflex condenser, (5) Total mass of reject mixture, (6) Concentration of reject mixture, (7) Enthalpy of reject mixture, (8) The heat gained by the generator is given by equation (9) and heat supplied by reheater is given by equation (10). Equation (11) provides the heat rejected by heater and (12) gives the heat absorbed by evaporator. Coefficient of performance for heater and evaporator are given by (13) and (14) respectively. Energy utilization factor of the cycle can be determined by equation (15). Heat input to generator, (9) Heat supplied by reheater, (10) Research Journal of Engineering Sciences ___________ _________ _____ __________________ ______ ____ ___ ISSN 2278 – 9472 Vol. 2 ( 7 ), 10 - 14 , Ju ly (201 3 ) Res. J. Engineering Sci. International Science Congress Association 12 Heat rejected by condenser cum heater, (11) Heat absorbed by evaporator, (12) Coefficient of performance of heater, (13) Coefficient of performance of evaporator, (14) Energy utilization of cycle, (15) Results and Discussion With alterations in the vapor absorption refrigeration cycle, improved results were obtained. Figure - 2 presents variation of cooling output with thermic fluid temperature available from the heat recovery source. For increasing thermic fluid temperature, in crease in cooling output was observed. Maximum output of 554.44 kW was attained for weak solution concentration of 0.96 at an ambient temperature of 20 °C and t hermic fluid temperature of 170 °C. Although the output for varying weak solution concentration re duces with increase in concentration, the plot presents marginal difference in cooling output at increasing thermic fluid temperature. It should be noticed that ambient temperature influences the obtained plot a great extent. With increase in ambient tempe rature from 20°C to 35 °C, cooling output for each concentration reduces nearly by 25 %. Also, higher temperature ranges are required to attain maximum cooling output. The variation of heating output with varying atmospheric temperature, thermic fluid temp erature and weak solution concentration is presented in figure - 3. Following the same pattern and distribution as in figure - 2, the process heat output increases with decrease in weak solution concentration. Also, the output reduces with increasing atmospher ic temperature. Fo r heat input temperature of 170°C, ambient condition of 20 °C and weak solution concentration of 0.96, highest value of 732.05 kW was obtained. In figure - 4, distribution of energy utilization factor has been exhibited. Figure - 2 Cooling output vs. Thermic fluid temperature (T 22 ) Research Journal of Engineering Sciences ___________ _________ _____ __________________ ______ ____ ___ ISSN 2278 – 9472 Vol. 2 ( 7 ), 10 - 14 , Ju ly (201 3 ) Res. J. Engineering Sci. International Science Congress Association 13 Figure - 3 Process heat output vs. Thermic fluid temperature (T 22 ) Figure - 4 Total output vs. Energy utilization factor Research Journal of Engineering Sciences ___________ _________ _____ __________________ ______ ____ ___ ISSN 2278 – 9472 Vol. 2 ( 7 ), 10 - 14 , Ju ly (201 3 ) Res. J. Engineering Sci. International Science Congress Association 14 Energy utilization factor gives the overall efficiency of the cycle, considering both cooling and heating outputs. As efficiency increases with increase in output, higher efficiencies were attained at higher values of heat input temperature. From figure - 4, it can be inferred that ambient temperature of 20°C with thermic fluid temperature of 170°C and weak solution concentration of 0.96 proves to be the most optimum condition for functioning of proposed cogeneration cycle. Maximum output of 1284.49 kW with energy utilization factor of 1.193 was attained. Key perfo rmance parameters of the cycle at the optimum condition are presented in table - 1. Table - 1 Key performance parameters of the cycle at the optimum condition Point P (bar) T (°C) x m (kg/s) h (kJ/kg) 1 2.9 25 0.496 1.00 - 133.91 2 9.7 25.11 0.496 1.00 - 132.81 3 9.7 73.45 0.496 1.00 90.50 4 9.7 150 0.496 1.00 475.48 5 9.7 150 0.100 0.49 578.08 6 9.7 150 0.880 0.51 1740.95 7 9.7 145 0.117 0.05 546.28 8 9.7 149.56 0.102 0.54 575.24 9 9.7 99.16 0.102 0.54 353.46 10 2.9 99.26 0.102 0.54 353.46 11 9.7 145 0.960 0.46 1640.58 12 9.7 145 0.960 0.46 1640.58 13 9.7 160 0.960 0.46 1677.69 14 9.7 25 0.960 0.46 86.16 15 2.9 - 10 0.960 0.46 86.16 16 2.9 - 10 0.960 0.46 1291.54 Comparing to the similar work on vapor absorption refrigeration system by Shankar and Srinivas, much higher cooling output is obtained in the present work 3 . But, the power generation overshadows the presented work as it involves pressure reduction. Vapor absorption refrigeration based cogeneration system presents itself highly e fficient on the contrary to cogeneration systems based on vapor compression refrigeration 1 . Although there have been many modifications and optimization of vapor absorption refrigeration systems, the obtained results validate efficient performance of propo sed cycle. Also, the proposed vapor absorption cogeneration cycle calls for further research and development to augment the technology. Conclusion For the present work, optimum functioning delivered process heat of 732.05 kW with cooling effect of 554.44 kW a t atmospheric temperature of 20 °C, heat input temperature of 170 °C and weak solution concentration of 0.96. Simulation analysis of the proposed cycle also exhibited an energy utilization factor of 1.193 at best condition. The use of reheater for addit ional heat input and condenser as heat rejecter with incorporation of heat exchanger for pre - heating of working fluid at generator inlet, presents itself viable for application, and advance research and development involving exergy analysis as well. Refer ences 1. Agarwal P., Shankar R. and Srinivas T., Design of integrated R134a vapor compression heating and cooling cycle, Emerging Trends in Science, Engineering and Technology, Proceedings of Internaional Conference, INCOSET 2012, 47 - 54 (2012) 2. Karagoz S., Yil maz M., Comakli O. and Ozyurt O., R134a and various mixtures of R22/R134a as an alternative in vapor compression heat pumps, Energy Cons. Mngmt, 45 , 181 - 196 (2004) 3. Shankar R. and Srinivas T., Modeling of energy extraction in vapor absorption refrigeration system , Procedia Eng., 38 , 98 - 104 (2012) 4. Bakhtiari B., Fradette L., Legros R. and Paris J., Opportunities for the integration of absorption heat pumps in the pulp and paper process, Energy, 35 , 4600 - 4606 (2010) 5. Billiard F., Refrigerating Equipment, Energy Efficiency and Refrigerants, Bulletin of the International Institute of Refrigeration, 85(1) , 12 – 25 (2005) 6. Srinivas T., Gupta A.V.S.S.K. S. and Reddy B. V., Performance simulation of combined cycle with Kalina bottoming cycle, Cogeneration & Distributed Generation Journal , 23 (1) , 6 - 21 (2008) 7. Kalinowski P., Hwang Y., Radermacher R., Hashimi S. A. and P. Rodgers, Application of waste heat powered absorption refrigeration system to the LNG recovery process, Int. J. Refrig., 32(4) , 687 - 694 (2009) 8. Xu F. and G oswami D. Y., Thermodynamic properties of ammonia - water mixtures for power - cycle applications, Energy, 24 , 525 - 536 (1999) Nomenclature : h Specific enthalpy, kJ/kg m mass flow rate, kg/s T Temperature, °C P Pressure, bar x Concentration η pump Pump efficiency Q Heat, kW COP Coefficient of performance EUF Energy utilization factor